Skip to end of metadata
Go to start of metadata

You are viewing an old version of this page. View the current version.

Compare with Current View Page History

« Previous Version 5 Next »

© Copyright Rod Hughes Consulting Pty Ltd
Rod Hughes Consulting
General Web Site
 
Applications
Home
Innovations and
Solutions Home

A bit about
Rod Hughes
 Link to this page...

The URL in the browser address bar is volatile and may be broken at any time.

To obtain a link to this page, click the <<Share>> button top-right of the screen.

  

Note - if the navigation pane on the left of this window is not visible, click the 2-pane icon on the top bar



A fairly common question  is which side to star the CT or which side to have the polarity and if there are any consequences?

The answer, as always, depends on the application, and then to some extent on the capabilities and settings of the IEDs!

Non-directional Current Applications

If we consider "general" overcurrent and earth fault relays connected to CTs in a Holmgren connection, there are four possible combinations.


Polarity towards loadPolarity towards source
Star
source
side

Star

load

side


The relay itself only operates on the magnitude of the current so it does not care about which side of the CT is the star or which side is the polarity terminal. 

Specifically the relay does not care about the direction of current flow through its elements so all four scenarios operate the same.

Directional, Distance and Power- based Applications

However, if the "50" or "51" elements (IEEE C37-2008) are now directional as "67" devices, or perhaps a distance function "21", reverse/over power function "32", or any other power related function including metering etc, the direction of power flow becomes significant. 

Scenario 1 and 4 are the same as each other,  whilst scenarios 2 and 3 are also the same as each other, but 180 degrees opposite 1 and 4.

If the IED allows changing of the polarity seen by the IED as part of its available settings, the direction can be set to suit the application as part of commissioning.

Consequently the star side and the polarity of the CT is arguably insignificant in most modern applications and becomes a matter for convention in order to be consistent across the various locations simply to ensure there is no confusion for the technicians.

Differential Applications

This is arguably a little more complicated in the "it depends" consideration

Merz-Price Circulating Current


Holmgren or Low Impedance Connection


 

Course contact
Are you in need of specific training:
  • Protection Systems Engineering
  • IEC 61850 Engineering

I provide a range of courses for company-specific in-house training and occasional public invitation courses.  Contact me for details.


 

Contact Me

Email Me

A phone call is nearly always welcome depending on the time of night wherever I am in the world.
Based in Adelaide UTC +9:30 hours e.g.

April-SeptemberNoon UK = 2030 Adelaide
October-March:Noon UK = 2230 Adelaide

  Office + 61 8 7127 6357
  Mobile + 61 419 845 253


Extra Notes:

Disclaimer
No Liability:
Rod Hughes Consulting Pty Ltd accepts no direct nor consequential liability in any manner whatsoever to any party whosoever who may rely on or reference the information contained in these pages.  Information contained in these pages is provided as general reference only without any specific relevance to any particular intended or actual reference to or use of this information. Any person or organisation making reference to or use of this information is at their sole responsibility under their own skill and judgement.

No Waiver, No Licence:
This page is protected by Copyright ©
Beyond referring to the web link of the material and w
hilst the information herein is accessible "via the web", Rod Hughes Consulting Pty Ltd grants no waiver of Copyright nor grants any licence to any extent  to any party in relation to this information for use, copy, storing or redistribution of this material in any form in whole or in part without written consent of Rod Hughes Consulting Pty Ltd.


  • No labels