In many discussions about selection and use of IEDs for IEC 61850, the subject of compliance is often raised. 

Compliance is certified by certain approved testing agencies which are controlled by the UCAIUG.

The current list of Type A (vendor independent) and Type B (vendor specific) test houses is published by UCAIUG here.

KEMA, as one of the authorised test houses, has their own register of Conformance Certificates issued by KEMA here

Up until 2010, Certification clearly referred to Edition 1 of the parts of the Standard available at that time.

As at December 2012, there is no official published IEC 61850 Part 10 Ed2 - this means there are no official new test procedures as yet.

The particular parts that are tested are Parts 6, 7, 8 and 9 as appropriate to the IED and as may be requested by the vendor.  You may be familiar with the certification wording:

Naturally any Certificate is relative to the Standard as available at the time.  In the case of IEC 61850, there may be modifications to the Standard determined out of the specific release of any new Edition which is managed and documented through the TISSUE process.  Consequently it is vital to cosnider any Certification statement in terms of the date of issue and any TISSUES since the relevant Edition of those Parts that are claimed to have been incorporated by the vendor as stated in the TISSUES Implementation Conformance Statement (TICS)

However since 2010, certain Parts of the Standard have been issued as Edition 2 and hence there can be different interpretations of what is meant by "the IED is conforming to IEC 61850" in general and even in respect of which Parts it is conforming to and which Edition of those Parts.

As an example an IED may well conform to the Edition 1 or even Edition 2 of the four Parts of IEC 61850-7-1, 7-2, 7-3, 7-4 Data Models but not conform to new features associated with Edition 2 of Parts 6, 8 or 9.

Warning
In the mean time as an example, it is unclear from the wording on the Conformance Certificate itself if a Certification for Part 8-1 issued in say December 2011 refers to the original 8-1 Ed1 or 8-1 Ed2 as issued in June 2011.

It is therefore not sufficient to simply state as a specification requirement "all IEDs shall conform to IEC 61850".

In fact the detail of the specification of an IEC 61850 System and/or the IEDs should not be underestimated: Specifying IEC 61850 Systems and/or IEDs

The following table indicates the current Edition status of the Parts of the Standard, and the future proposed Edition 1 or Edition 2 of other Parts of the Standard. As further work is done to improve and expand the Standard, there will be times when the current Editions are a combination of  Edition 1, Edition 2 and Edition 3 etc amongst the Parts.

PartReleased yyyy-mmDue Date 

1

Ed1 2003-04

 

Introduction and overview

2

Ed1 2003-08

 Glossary

3

Ed1 2002-01  (Ed2 2013-09)

 General Requirements

4

 System and Project Management

5

Ed1 2003-07 (Ed2 2013-01)

 Communication requirements for functions and device models

6

 Configuration description language for communication in electrical substations related to IEDs

7-1

 

Basic communication structure – Principles and models

7-2

 

Basic information and communication structure – Abstract communication service interface (ACSI)

7-3

 

Basic communication structure – Common data classes

7-4

 

Basic communication structure – Compatible logical node classes and data object classes

7-410

Ed1 2007-08

 

Hydroelectric power plants – Communication for monitoring and control

7-420

Ed1 2009-03

 

Basic communication structure – Distributed energy resources logical nodes

8-1

 

Specific communication service mapping (SCSM) – Mappings to MMS (ISO 9506-1 and ISO 9506-2) and to ISO/IEC 8802-3

9-1

 

Specific Communication Service Mapping (SCSM) – Sampled values over serial unidirectional multidrop point to point link

9-2

 

Specific communication service mapping (SCSM) – Sampled values over ISO/IEC 8802-3

9-2LE

R2-0a 2004-03 

Implementation Guideline For Digital Interface To Instrument Transformers

10

Ed1 2005-05 (Ed2 2013-01)

 Conformance Testing

80-1

Ed1 2008-12

 

Guideline to exchanging information from a CDC-based data model using IEC 60870-5-101 or IEC 60870-5-104

90-1

Ed1 2010-03

 

Use of IEC 61850 for the communication between substations

7-5

  

Use of logical nodes to model applications – generic principles

7-500

  

Use of logical nodes to model applications in substations

8-2

 

Ed1 2014-01

Mapping on web services

80-2

 

Ed1 2014-01

IEEE 1815-1  DNP3 Mapping

90-1

  

Use of IEC 61850 for the communication between substations

90-2

   

90-3

   

90-4

  

Network engineering guidelines for substations

90-5

  

Use of IEC 61850 to transmit synchrophasor information according to IEEE C37.118

90-6

  

Using 61850 for distribution automation

90-7

  

IEC 61850 object models for photovoltaic, storage and other DER inverters

90-8

   

90-9

   

90-10

   

90-11

   

90-11

   

90-12

   

90-13

 

Ed1 2015-01

logical nodes and data models for steam and gas turbines

90-14

   

90-15

  

Implementation Guideline For Digital Interface To Instrument Transformers

100-1

  

Methodologies for testing of functions in IEC 61850 based systems

 ?  

System management

 ?  

Alarm handling

 ?  

FACTS

 ?  

Preparation of UML model for IEC 61850

Column
width2%
 

A list of the parts of the Standard is available here Parts and associated Standards