Versions Compared

Key

  • This line was added.
  • This line was removed.
  • Formatting was changed.

...

Section


Column

Differential protection in principle is straight forward - what goes in, should come out! 
If there is a difference there is a fault.

The IEEE C37.2 reference number for this is 87.
IEC 61850 uses the PDIFF Logical Node.

This can be applied to a busbar, a generator or motor winding, transformer or to a power line. Due to the distances involved, line differential requires special techniques (not discussed here) to compare the current at each end .

Using CTs to measure the current at each end of the unit of power system we wish to protect - and hence differential is referred to as unit protection - we can now compare these currents.

In the case of any winding differential scheme - i.e. associated with a generator winding, motor winding or transformer winding the differential scheme may be a specific arrangement known as Restricted Earth Fault (REF) which only detects earth fault within the CT zone - phase to phase faults are not detected.

Modern times have seen a move to microprocessor based relays where individual CT cores at each end are connected directly to individual inputs on the relay.  The relay then uses numerical techniques to sum the currents as required.

However the principles of differential protection were borne in the application of the so called circulating current Merz-Price connection.  This allows us to use the CT connections to circulate any through current around the CTs as shown on this page: High Impedance, Merz-Price, Circulating Current Differential

In the case of transformers with the Merz-Price arrangement, things are more complicated because the currents on the HV side of the transformer may be different to the currents on the LV side so simple comparison is not possible - care must be taken to connect the CTs in the right arrangement to cater for not only ratio differences but also transformer vector shifts.

  • In the case of REF schemes we must connect the CTs in parallel to each other and the relay.
  • In the case of the overall transformer differential, the vector correction means that the delta side CTs are connected in star, whilst the star side CTs are connected in delta.

Due to these mutually exclusive CT connection arrangements it is not possible to directly connect the REF relay and overall differential relay to the same CT cores. 
The following diagrams (click to enlarge) show the current flows associated with a phase-to-earth and phase-to-phase fault fault on the star side. 

If there is only a single set of CTs available, it is therefore necessary to use an Interposing CT (not shown) to "split" the current from the single CT cores to be able to be connected in the right arrangements. Examples of this interposing CT arrangement is given in the Alstom "Network Protection Application Guide" book, Figure 16.13 and 16.14 of the May 2011 Edition.

Even in star-star transformers we cannot use a single set of CTs on each side. 
As we can see the REF schemes on each side have all the CTs directly connected on their S1 and S2 terminals. 
The overall differential cores however are connected phase-by-phase.

If the REF and the TF diff relays are connected to the same set of CT cores, the following individual situations occur:

  1. the TF diff will loose its phase discrimination since all the S1 of all six CTs are are joined together.
  2. The REF elements will lose their HV - LV discrimination, again because all S1 terminals are joined together and both elements are in parallel.
  3. There would now be five relay elements all connected in parallel to the six CT cores connected in parallel.  Hence the internal fault current will split down each of the relay elements according to their respective impedances.  Hence there would be a severe reduction in sensitivity, although of course these elements generally have low settings of say 10% of rated current compared to maximum fault currents of 20 x rated.  This problem can be reduced if the individual phase elements and on eof the REF elements are discarded (they are all in parallel anyway) but then it is just one element with no discrimination of the fault location which was the original reason for having the TF diff and separate REF on each winding.

 

 

 

 






Column
width2%
 


Column
width18%

Copy this permanent link to this page https://rhconsult.tiny.us/bdfbrjeh


Insert excerpt
FAQ:Contact Me
FAQ:Contact Me
nopaneltrue


Extra Notes:


...