I have heard/seen people talk about the load becoming soooo inductive that the lag angle becomes >90 degrees
Obviously that is absolute rubbish!

But we do talk about reverse power flow.
Some would then say that power flow is towards the source or the source has negative resistance
Again, absolute rubbish!

There is a fundamental principle that energy can ONLY flow from the source to the consumer
I can accept that a load like a motor may suddenly be driven by the inertia of the mechanical load to become a generator back to other loads on the grid … but it is no longer the load end, it is the source end, so the overall flow of power has reversed in that instance.
Equally in a multi-source, multi-load grid, any particular line can experience energy transfer in either direction.

So what IS reverse power flow?????????????

Well, this spreadsheet explains it as simply related to the polarity of the CTs at the two ends of a line.

Yes, … it depends on what you have deemed as "forward" power flow versus "reverse" power flow direction!!!

You can select resistive, inductive or capacitive load in the yellow cell.
We can see that the operating P:Q position is in the opposite quadrant at each end of the line!  i.e. although the net transfer of energy is in one direction, our point of view at each end would say one direction is reversed compared to the other.
… and again as we would expect, the mathematics prove that PF is positive at both ends of the line despite a negative P at one end!
We can see that full 360o cos(φ) meters need to have a range from -1 to 0 to +1
However Power Factor Meters will only read in the range 0 to +1, despite operating in the four quadrants as lag or lead.

So, again as we would expect, this proves that statements such as “negative PF only means reverse power flow” is fundamentally wrong, simply because Negative PF can’t exist.

However, negative P or a negative cosPhi (with Phi being angle of I with respect to V) - which is not the same as PF in all circumstances - means that the Source is in front of the arbitrary forward power direction determined by the CT polarity.

THEN, that deals with the conundrum of the idea that reverse power flow means negative resistance … that is just a mathematical "equivalent" based on "reverse engineering" R = P/I2 … negative resistance don’t exist in real life either, but it can mathematically!

 

Course contact
Are you in need of specific training:
  • Protection Systems Engineering
  • IEC 61850 Engineering

I provide a range of courses for company-specific in-house training and occasional public invitation courses.  Contact me for details.


 

Contact Me

Email Me

A phone call is nearly always welcome depending on the time of night wherever I am in the world.
Based in Adelaide UTC +9:30 hours e.g.

April-SeptemberNoon UK = 2030 Adelaide
October-March:Noon UK = 2230 Adelaide

   Mobile + 61 419 845 253


Extra Notes:

Disclaimer
No Liability:
Rod Hughes Consulting Pty Ltd accepts no direct nor consequential liability in any manner whatsoever to any party whosoever who may rely on or reference the information contained in these pages.  Information contained in these pages is provided as general reference only without any specific relevance to any particular intended or actual reference to or use of this information. Any person or organisation making reference to or use of this information is at their sole responsibility under their own skill and judgement.

No Waiver, No Licence:
This page is protected by Copyright ©
Beyond referring to the web link of the material and w
hilst the information herein is accessible "via the web", Rod Hughes Consulting Pty Ltd grants no waiver of Copyright nor grants any licence to any extent  to any party in relation to this information for use, copy, storing or redistribution of this material in any form in whole or in part without written consent of Rod Hughes Consulting Pty Ltd.