Converting Measured Values to Sequence ComponentsPositive, Negative and Zero Sequence Components are often a key aspect of analysis of power system conditions.
Any set of three phase measurements of Magnitude AND Relative Phase Angle between the phasors can be analysed using the Sequence Component Formulas: - Positive Sequence A = ( A + αB + α²C ) / 3
- Negative Sequence A = ( A + α²B + αC ) / 3
- Zero Sequence A = ( A + B + C ) / 3
where the measured values are magnitude and relative phase angle values compared to the reference 0° angle. - A = A_magnitude @ A_angle (A_angle can often be stated as 0 as a "reference" phasorangle is with respect to the reference angle, but is often set as the reference phasor at 0°)
- B = B_magnitude @ B_angle (B_angle is with respect to the A phasorreference angle)
- C = C_magnitude @ C_angle (C_angle is with respect to the A phasorreference angle)
- α = 1 @ 120°
Note these relative phase angles are NOT the phase angle associated with Power Factor. Power Factor angle refers to the relationship between voltage and current which is distinctly different to the angle relationship between the three currents or angle relationship between the three voltages. These formulas allow us to derive nine Sequence Component Phasors Positive Sequence (generally designated as a suffix "1") A1 = A1_magnitude @ A1_angle B1 = B1_magnitude @ B1_angle C1 = C1_magnitude @ C1_angle where - A1_magnitude = B1_magnitude = C1_magnitude
- B1_angle = A1_angle - 120
- C1_angle = B1_angle - 120
Negative Sequence (generally designated as a suffix "2") A2 = A2_magnitude @ A2_angle B2 = B2_magnitude @ B2_angle C2 = C2_magnitude @ C2_angle where - A2_magnitude = B2_magnitude = C2_magnitude
- B2_angle = A2_angle - 120
- C2_angle = B2_angle - 120
Zero Sequence (generally designated as a suffix "0") A0 = A0_magnitude @ A0_angle B0 = B0_magnitude @ B0_angle C0 = C0_magnitude @ C0_angle where - A0_magnitude = B0_magnitude = C0_magnitude
- A2_angle = B2_angle = C2_angle (all in phase)
This spread sheet provides a tool for converting the 3-phase phasors into their Sequence Components. Click to download the spreadsheet: Sequence Components.xlsx Analysis examplesFor a balanced condition, all phases are equal magnitude and 120 degrees separation in the right sequence and would therefore be analysed as pure Positive Sequence, no Negative or Zero Sequence. This would remain true at any value of the balanced phasors and hence we must take care in setting protection functions not to operate for balanced loads from zero to rated values, and knowing that even large changes below rated values are not necessarily indicative of an actual fault. However if the phasors become unbalanced for any reason ,i.e. no longer equal magnitude and/or no longer 120 degrees separation, Negative Sequence and/or Zero sequence will be seen which will be a very clear indication of some kind of fault - they are normally zero but become non-zero. Hence some functions are assigned to operate on the basis of Negative Sequence detection changing from zero. Of course Zero Sequence detection has always been available as the earth fault element. Older electro-mechanical relays required complicated extra hardware filters to extract Negative Sequence component. The advent of numerical relays has provided easier detection of Sequence Components using algorithms. Sequence Components are mathematical analysis of a set of three phasors. They are not "real" world physical measurements. You cannot connect a multi-meter to any point and measure a Sequence Component! Even if you use a multi-meter to measure all three phases as the same magnitude, you also need to know they are exactly 120° apart to know that the values are balanced and therefore would be the Positive Sequence value with no Negative or Zero Sequence component. - The "closest" you get is if you know there is no current in two of the three phases but current in the third, you know the third current is 3 x the Zero Sequence.
- Or if you measure the current in the earth-neutral leg, that current is 3 x the Zero Sequence.
- Or the current in the delta itself is the actual Zero Sequence value IF all three windings are the same magnitude AND they must also be in-phase (consider a Dyn TF with balanced load .. the D winding currents are all the same magnitude but not in-phase).
Example 1: Balanced 3-phase is all positive sequence
Example 2: general unbalance magnitudes and angles results in a full set of Sequence Components
Example 3: a single phase condition would result in these components (e.g. the star side of a Dyn transformer with a single phase load or fault on the star, or the currents in the delta windings):
Example 4: a phase-to-phase condition would result in these components: (e.g. the line connections to the delta side of a Dyn transformer with a single phase load or fault on the star)
Example 5: unequal single-phase Power Factors e.g. assuming the phase-to-neutral voltages are all balanced at 120 degrees apart and A phase voltage is reference 0°: A_phase 0.95 lagging (-18°) means the A phase current phasor is at -18° with respect to the A phase voltage, B_phase 0 PF, means the B phase current is in phase with the B phase voltage, i.e. at -120° with respect to the A phase voltage, C_phase 0,85 leading (+31°) means the C phase current is leading the C phase voltage by 31°, i.e. -209° with respect to the A phase voltage
A common question when first dealing with Sequence Components is : How are Zero Sequence current eliminated in delta windings. First you have to remember that Sequence Components are not “real” – they are mathematical derivations from the real currents, but the sum of all Components add up to equal the real currents. Hence for a set of 3 phase phasors, there are nine Sequence Component phasors: 3 x Positive Sequence, 3 x Negative Sequence and 3 x Zero Sequence. Second, real currents must obey Ohm’s Law and Kirchoff’s Law … they must have a path to flow. So do Sequence Components, but the real paths have to be converted into equivalent Sequence Component paths and equivalent Sequence Component impedances, although that is not the focus of this information. YNynConsider a low voltage star winding of a transformer. Single phase current can flow if there is a connection to the star (neutral) point of the transformer … - 4‑wire systems of course mean single phase loads can have current in one phase flowing back via the neutral wire.
- 3-wire, or 4-wire systems with earthed neutral will allow single phase earth fault currents to flow in one phase flowing back via the earth.
So the real current distribution of a single phase condition (load or earth fault), the three phases would be termed “1-0-0”. Refer Example #3 above. With current in one phase, the Sequence Component Analysis shows that there is Positive, Negative and Zero Sequence current flowing in all three phases and they “flow” through the equivalent three phase Positive, Negative and Zero Sequence path impedance of each phase, even though the real impedance on the two phases with zero real current is effectively an open circuit. The A, B and C zero sequence currents would all add up to be the value of the real current because as zero sequence they are all in phase. i.e. I-single-phase = 3 x I-zero-sequence So now consider that single phase LV current in a star winding for a YNyn arrangement, i.e. neutral connections on both windings On a star HV winding, that LV current must cause equal Ampere.Turns balance on the HV winding, i.e. real current in one LV winding needs to cause real current in one HV winding to maintain Ampere.Turns balance. Being a star HV winding arrangement, there can only be current flowing in one HV winding corresponding to the LV winding with real current flow. There can be no current in the other two HV windings because there is no current in the other two LV windings. That being the case, then the real HV currents would also be termed “1-0-0” distribution and would also be analysed with Positive, Negative and Zero Sequence components. DynIf the HV winding is delta, i.e. Dyn, Ampere.Turns must still balance LVwinding-to-HVwinding. So one of the delta limb windings will have current flowing to balance its corresponding LV winding. At each bushing there are three connections – two winding ends and the line. Kirchoff’s Law is that the sum of the currents in and out of a node must equal zero. We know that one winding has current flow, the other winding has none, so the current flow must be on the line connected to the node. That happens because when you look at the currents in the windings (i.e. not the line currents), the winding currents are still “1-0-0” due to Ampere.Turns balance. That HV winding current can only flow into the TF bushing from one phase connection and out on another phase connection at the other end of the winding, i.e. there is line current flowing "into" the bushing on A phase and out of the other bushing on B phase. We would therefore term the line currents as a “1-1-0” where the two line currents are equal magnitude and opposite directions. If you now do the Sequence Components of a “1-1-0” as in Example #4 above, you will see that there is only Positive and Negative Sequence … no Zero Sequence at all. We therefore say that the Delta winding is a "Zero Sequence Trap".
The delta winding currents ar "1-0-0" distribution to achieve Ampere.Turns balance with the LV windings. That means that within the windings, there are Positive, Negative and Zero Sequence components. Therefore the magnitude and phase angle of the A winding, B winding and C winding Zero Sequence currents are all exactly the same. Therefore applying Kirchoff’s Law, if the current flowing into the node from one winding equals the current flowing out of the node into the other winding, there can be no Zero Sequence current flowing on the line as proven in the previous paragraph. All the Zero Sequence currents happily flow around the HV Delta winding, but do not flow on the HV line phases. Hence the Delta has "trapped" the zero sequence current. (For the same reason, delta windings are also a 3rd harmonic trap as the 3rd harmonics are inherently in phase.) But note: a common misunderstanding is that Delta windings do not result in any zero sequence current .. ever! If you have an earth fault on the HV delta winding,.., in the worst case say a bushing to earth, there will be current flowing down the one line to the faulted bushing. That would still be “1-0-0” so Zero Sequence still exists. Mid-winding faults would be more complicated with real currents flowing in all three lines, but will still analyse as having some Zero Sequence. |